| Industrial Cables | |||
Industrial Cables
Industrial PVC Insulated Cables
Instrumentation Cable (300 Volt)
PVC/PVC Instrumentation Cable with Overall Shielded Pairs/Triads
Applications:
Acceptable for use in free air or raceways in accordance with NEC
Typical applications include audio, intercom, control, energy management and alarm circuits.
In ducts, cable trays or conduit
In accordance with UL Subject 13 as Power-Limited Circuit Cable
In class 3 circuits in accordance with NEC
In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC Article 501-4(b) for UL Type PLTC/ITC cables
Per NEC Article 727 for Type PLTC/ITC
Construction:
Conductor: 20 AWG thru 16 AWG bare, annealed copper per ASTM B3 ,Class B stranding per ASTM B8
Insulation: Polyvinyl Chloride (PVC) ,Color-coded per ICEA Method 1:
Pairs: Black and White
Triads: Black, White and Red
Shield: Overall shielded pairs/triads ,Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
Jacket: Flame-retardant and sunlight-resistant Polyvinyl Chloride (PVC)
Options: Tinned copper conductor; Class C Stranding; Other constructions available upon request
Approvals:
Industry Compliances:
UL 13 Type PLTC/ITC
Flame Tests Compliances:
IEEE 383 (70,000 BTU/hr)
UL Subject 13 (70,000 BTU/hr) for PLTC
UL Subject 2250 (70,000 BTU/hr) for ITC
Other Compliances:
Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
OSHA acceptable
AWG Size |
Conductor Stranding |
No. of Pairs |
No. of Triads |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. of Cable (in) |
Approx LBS/MFT |
20 |
7/0.0121 |
1 |
|
0.012 |
0.04 |
0.22 |
28 |
20 |
7/0.0121 |
|
1 |
0.012 |
0.04 |
0.241 |
34 |
20 |
7/0.0121 |
2 |
|
0.012 |
0.04 |
0.255 |
41 |
20 |
7/0.0121 |
4 |
|
0.012 |
0.042 |
0.321 |
65 |
20 |
7/0.0121 |
8 |
|
0.012 |
0.05 |
0.475 |
104 |
20 |
7/0.0121 |
12 |
|
0.012 |
0.05 |
0.545 |
195 |
20 |
7/0.0121 |
16 |
|
0.012 |
0.05 |
0.605 |
248 |
20 |
7/0.0121 |
20 |
|
0.012 |
0.06 |
0.65 |
309 |
20 |
7/0.0121 |
24 |
|
0.012 |
0.06 |
0.74 |
376 |
20 |
7/0.0121 |
36 |
|
0.012 |
0.06 |
0.85 |
530 |
20 |
7/0.0121 |
50 |
|
0.012 |
0.07 |
0.97 |
713 |
18 |
7/0.0152 |
1 |
|
0.015 |
0.04 |
0.24 |
35 |
18 |
7/0.0152 |
|
1 |
0.015 |
0.04 |
0.264 |
44 |
18 |
7/0.0152 |
2 |
|
0.015 |
0.042 |
0.325 |
55 |
18 |
7/0.0152 |
4 |
|
0.015 |
0.042 |
0.357 |
90 |
18 |
7/0.0152 |
8 |
|
0.015 |
0.06 |
0.646 |
192 |
18 |
7/0.0152 |
12 |
|
0.015 |
0.06 |
0.67 |
293 |
18 |
7/0.0152 |
16 |
|
0.015 |
0.06 |
0.75 |
374 |
18 |
7/0.0152 |
20 |
|
0.015 |
0.06 |
0.78 |
449 |
18 |
7/0.0152 |
24 |
|
0.015 |
0.07 |
0.915 |
564 |
18 |
7/0.0152 |
36 |
|
0.015 |
0.07 |
1.03 |
787 |
18 |
7/0.0152 |
50 |
|
0.015 |
0.07 |
1.18 |
1059 |
16 |
7/0.0192 |
1 |
|
0.015 |
0.04 |
0.273 |
45 |
16 |
7/0.0192 |
|
1 |
0.015 |
0.042 |
0.297 |
58 |
16 |
7/0.0192 |
2 |
|
0.015 |
0.042 |
0.344 |
74 |
16 |
7/0.0192 |
4 |
|
0.015 |
0.053 |
0.481 |
132 |
16 |
7/0.0192 |
8 |
|
0.015 |
0.06 |
0.726 |
259 |
16 |
7/0.0192 |
12 |
|
0.015 |
0.06 |
0.755 |
408 |
16 |
7/0.0192 |
16 |
|
0.015 |
0.07 |
0.845 |
526 |
16 |
7/0.0192 |
20 |
|
0.015 |
0.07 |
0.905 |
655 |
16 |
7/0.0192 |
24 |
|
0.015 |
0.07 |
1.03 |
803 |
16 |
7/0.0192 |
36 |
|
0.015 |
0.07 |
1.165 |
1122 |
16 |
7/0.0192 |
50 |
|
0.015 |
0.08 |
1.355 |
1544 |
Applications
Acceptable for use in free air or raceways in accordance with NEC
Typical applications include audio, intercom, control, energy management and alarm circuits.
In ducts, cable trays or conduit
In accordance with UL Subject 13 as Power-Limited Circuit Cable
In class 3 circuits in accordance with NEC
In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC Article 501-4(b) for UL Type PLTC/ITC cables
Per NEC Article 727 for Type PLTC/ITC
Construction
Conductor:
20 AWG thru 16 AWG bare, annealed copper per ASTM B3
Class B stranding per ASTM B8
Insulation:
Polyvinyl Chloride (PVC)
Color-coded per ICEA Method 1:
Pairs: Black and White
Shield:
Individual and overall shielded pairs
Individual pairs are 100% shielded with aluminum/polyester in contact with stranded tinned copper drain wire
Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
Jacket:
Sunlight-resistant Polyvinyl Chloride (PVC)
Options:
Tinned copper conductor
Class C Stranding
Other constructions available upon request
Approvals
Industry Compliances:
UL 13 Type PLTC/ITC
Flame Tests Compliances:
IEEE 383 (70,000 BTU/hr)
UL Subject 13 (70,000 BTU/hr) for PLTC
UL Subject 2250 (70,000 BTU/hr) for ITC
Other Compliances:
Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
OSHA acceptable
Product Parameter
AWG Size |
Conduct or Stranding |
No. of Pairs |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. of Cable (in) |
Approx LBS/MFT |
20 |
7/0.0121 |
2 |
0.012 |
0.04 |
0.316 |
46 |
20 |
7/0.0121 |
4 |
0.012 |
0.042 |
0.325 |
76 |
20 |
7/0.0121 |
8 |
0.012 |
0.05 |
0.426 |
148 |
20 |
7/0.0121 |
12 |
0.012 |
0.06 |
0.64 |
223 |
20 |
7/0.0121 |
16 |
0.012 |
0.06 |
0.705 |
280 |
20 |
7/0.0121 |
20 |
0.012 |
0.06 |
0.78 |
339 |
20 |
7/0.0121 |
24 |
0.012 |
0.06 |
0.845 |
397 |
20 |
7/0.0121 |
36 |
0.012 |
0.07 |
1.015 |
586 |
20 |
7/0.0121 |
50 |
0.012 |
0.07 |
1.19 |
786 |
18 |
7/0.0152 |
2 |
0.015 |
0.042 |
0.296 |
61 |
18 |
7/0.0152 |
4 |
0.015 |
0.042 |
0.41 |
100 |
18 |
7/0.0152 |
8 |
0.015 |
0.06 |
0.485 |
212 |
18 |
7/0.0152 |
12 |
0.015 |
0.06 |
0.76 |
315 |
18 |
7/0.0152 |
16 |
0.015 |
0.06 |
0.845 |
401 |
18 |
7/0.0152 |
20 |
0.015 |
0.07 |
0.955 |
505 |
18 |
7/0.0152 |
24 |
0.015 |
0.07 |
1.04 |
596 |
18 |
7/0.0152 |
36 |
0.015 |
0.07 |
1.215 |
846 |
18 |
7/0.0152 |
50 |
0.015 |
0.08 |
1.45 |
1165 |
16 |
7/0.0192 |
2 |
0.015 |
0.042 |
0.346 |
80 |
16 |
7/0.0192 |
4 |
0.015 |
0.053 |
0.506 |
151 |
16 |
7/0.0192 |
8 |
0.015 |
0.06 |
0.665 |
288 |
16 |
7/0.0192 |
12 |
0.015 |
0.06 |
0.855 |
435 |
16 |
7/0.0192 |
16 |
0.015 |
0.07 |
0.97 |
575 |
16 |
7/0.0192 |
20 |
0.015 |
0.07 |
1.08 |
705 |
16 |
7/0.0192 |
24 |
0.015 |
0.07 |
1.165 |
828 |
16 |
7/0.0192 |
36 |
0.015 |
0.08 |
1.39 |
1215 |
16 |
7/0.0192 |
50 |
0.015 |
0.09 |
1.655 |
1670 |
PVC/PVC Instrumentation Cable with Individual and Overall Shielded Triads
Applications
Acceptable for use in free air or raceways in accordance with NEC
Typical applications include audio, intercom, control, energy management and alarm circuits.
In ducts, cable trays or conduit
In accordance with UL Subject 13 as Power-Limited Circuit Cable
In class 3 circuits in accordance with NEC
In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC Article 501-4(b) for UL Type PLTC/ITC cables
Per NEC Article 727 for Type PLTC/ITC
Construction
Conductor:
20 AWG thru 16 AWG bare, annealed copper per ASTM B3
Class B stranding per ASTM B8
Insulation:
Polyvinyl Chloride (PVC)
Color-coded per ICEA Method 1:
Pairs: Black and White
Triads: Black, White and Red
Shield:
Individual and overall shielded triads
Individual triads are 100% shielded with aluminum/polyester in contact with stranded tinned copper drain wire
Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
Jacket:
Sunlight-resistant Polyvinyl Chloride (PVC)
Options:
Tinned copper conductor
Class C Stranding
Other constructions available upon request
Approvals:
Industry Compliances:
UL 13 Type PLTC/ITC
Flame Tests Compliances:
IEEE 383 (70,000 BTU/hr)
UL Subject 13 (70,000 BTU/hr) for PLTC
UL Subject 2250 (70,000 BTU/hr) for ITC
Other Compliances:
Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
OSHA acceptable
Product Parameter
AWG Size |
Conductor Stranding |
No. of Triads |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. of Cable (in) |
Approx LBS/MFT |
20 |
7/0.0121 |
2 |
0.012 |
0.04 |
0.34 |
59 |
20 |
7/0.0121 |
4 |
0.012 |
0.04 |
0.365 |
97 |
20 |
7/0.0121 |
8 |
0.012 |
0.05 |
0.566 |
187 |
20 |
7/0.0121 |
12 |
0.012 |
0.06 |
0.705 |
287 |
20 |
7/0.0121 |
16 |
0.012 |
0.06 |
0.78 |
365 |
20 |
7/0.0121 |
20 |
0.012 |
0.06 |
0.86 |
440 |
20 |
7/0.0121 |
24 |
0.012 |
0.07 |
0.955 |
541 |
20 |
7/0.0121 |
36 |
0.012 |
0.07 |
1.115 |
767 |
18 |
7/0.0152 |
2 |
0.015 |
0.04 |
0.321 |
77 |
18 |
7/0.0152 |
4 |
0.015 |
0.05 |
0.444 |
143 |
18 |
7/0.0152 |
8 |
0.015 |
0.06 |
0.786 |
375 |
18 |
7/0.0152 |
12 |
0.015 |
0.06 |
0.84 |
412 |
18 |
7/0.0152 |
16 |
0.015 |
0.07 |
0.96 |
550 |
18 |
7/0.0152 |
20 |
0.015 |
0.07 |
1.06 |
668 |
18 |
7/0.0152 |
24 |
0.015 |
0.07 |
1.145 |
785 |
18 |
7/0.0152 |
36 |
0.015 |
0.08 |
1.365 |
1151 |
16 |
7/0.0192 |
2 |
0.015 |
0.04 |
0.367 |
104 |
16 |
7/0.0192 |
4 |
0.015 |
0.05 |
0.502 |
195 |
16 |
7/0.0192 |
8 |
0.015 |
0.06 |
0.786 |
375 |
16 |
7/0.0192 |
12 |
0.015 |
0.07 |
0.97 |
597 |
16 |
7/0.0192 |
16 |
0.015 |
0.07 |
1.075 |
765 |
16 |
7/0.0192 |
20 |
0.015 |
0.07 |
1.195 |
933 |
16 |
7/0.0192 |
24 |
0.015 |
0.08 |
1.31 |
1125 |
16 |
7/0.0192 |
36 |
0.015 |
0.08 |
1.54 |
1620 |