| Industrial Cables | |||
Industrial Cables
Instrumentation Cable (300 Volt)
XLPE/HYP Instrumentation Cable with Overall Shielded Pairs/Triads
Applications
Typical applications include audio, intercom, control, energy management and alarm circuits.
Acceptable for use in free air or raceways in accordance with NEC
In ducts, cable trays or conduit
Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC
In accordance with UL subject 13 as Power-Limited Circuit Cable
In class 3 circuits in accordance with NEC
Construction
Conductor:
20 AWG thru 16 AWG tinned, annealed copper per ASTM B33
Class B stranding per ASTM B8
Insulation:
Flame-retardant Cross-linked Polyethylene (XPLE)
Color-coded per ICEA Method 1:
Pairs: Black and White
Triads: Black, White and Red
Shield:
Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
Jacket:
Low-lead Hypalon Cholorsulfonated Polyethylene (CSPE)/Elastomer blend
Options:
Bare copper conductor
Class C Stranding
Individual and overall shielded pairs/triads
Thermoplastic, Low-Smoke, Zero-Halogen (LSZH) jacket
In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
Other constructions available upon request
Approvals
Industry Compliances:
UL 13 Type PLTC
UL 1581
Flame Tests Compliances:
UL 1581 VW-1
IEEE 383
IEEE 1202
CSA FT-4
Other Compliances
EPA 40 CFR, Part 261 for leachable lead content per TCLP
OSHA acceptable
Product Parameter
AWG Size |
Conductor Stranding |
No. of Pairs |
No. of Triads |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. (in) |
Approx LBS/MFT |
20 |
7/0.0121 |
1 |
|
0.012 |
0.035 |
0.23 |
27 |
20 |
7/0.0121 |
|
1 |
0.012 |
0.035 |
0.24 |
33 |
20 |
7/0.0121 |
2 |
|
0.012 |
0.04 |
0.32 |
48 |
20 |
7/0.0121 |
4 |
|
0.012 |
0.04 |
0.37 |
73 |
20 |
7/0.0121 |
8 |
|
0.012 |
0.05 |
0.5 |
138 |
20 |
7/0.0121 |
12 |
|
0.012 |
0.05 |
0.575 |
186 |
20 |
7/0.0121 |
16 |
|
0.012 |
0.06 |
0.665 |
248 |
20 |
7/0.0121 |
20 |
|
0.012 |
0.06 |
0.74 |
300 |
20 |
7/0.0121 |
24 |
|
0.012 |
0.06 |
0.765 |
350 |
20 |
7/0.0121 |
36 |
|
0.012 |
0.07 |
1.005 |
525 |
20 |
7/0.0121 |
50 |
|
0.012 |
0.07 |
1.175 |
697 |
18 |
7/0.0152 |
1 |
|
0.015 |
0.035 |
0.245 |
32 |
18 |
7/0.0152 |
|
1 |
0.015 |
0.035 |
0.255 |
40 |
18 |
7/0.0152 |
2 |
|
0.015 |
0.04 |
0.35 |
58 |
18 |
7/0.0152 |
4 |
|
0.015 |
0.05 |
0.425 |
99 |
18 |
7/0.0152 |
8 |
|
0.015 |
0.05 |
0.545 |
173 |
18 |
7/0.0152 |
12 |
|
0.015 |
0.06 |
0.64 |
245 |
18 |
7/0.0152 |
16 |
|
0.015 |
0.06 |
0.73 |
318 |
18 |
7/0.0152 |
20 |
|
0.015 |
0.06 |
0.81 |
392 |
18 |
7/0.0152 |
24 |
|
0.015 |
0.07 |
0.895 |
450 |
18 |
7/0.0152 |
36 |
|
0.015 |
0.07 |
1.095 |
672 |
18 |
7/0.0152 |
50 |
|
0.015 |
0.07 |
1.255 |
904 |
16 |
7/0.0192 |
1 |
|
0.015 |
0.035 |
0.27 |
41 |
16 |
7/0.0192 |
|
1 |
0.015 |
0.035 |
0.285 |
54 |
16 |
7/0.0192 |
2 |
|
0.015 |
0.05 |
0.43 |
85 |
16 |
7/0.0192 |
4 |
|
0.015 |
0.05 |
0.49 |
135 |
16 |
7/0.0192 |
8 |
|
0.015 |
0.06 |
0.65 |
246 |
16 |
7/0.0192 |
12 |
|
0.015 |
0.06 |
0.755 |
346 |
16 |
7/0.0192 |
16 |
|
0.015 |
0.06 |
0.845 |
444 |
16 |
7/0.0192 |
20 |
|
0.015 |
0.06 |
0.9 |
552 |
16 |
7/0.0192 |
24 |
|
0.015 |
0.07 |
1.02 |
655 |
16 |
7/0.0192 |
36 |
|
0.015 |
0.07 |
1.225 |
649 |
16 |
7/0.0192 |
50 |
|
0.015 |
0.08 |
1.415 |
1308 |
XLPE/HYP Instrumentation Cable with Individual and Overall Shielded Pairs
Applications
Typical applications include audio, intercom, control, energy management and alarm circuits.
Acceptable for use in free air or raceways in accordance with NEC
In ducts, cable trays or conduit
Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC
In accordance with UL subject 13 as Power-Limited Circuit Cable
In class 3 circuits in accordance with NEC
Construction
Conductor:
20 AWG thru 16 AWG tinned, annealed copper per ASTM B33
Class B stranding per ASTM B8
Insulation:
Flame-retardant Cross-linked Polyethylene (XPLE)
Color-coded per ICEA Method 1:
Pairs: Black and White
Shield:
Individual and overall shielded pairs
Individual pairs are 100% aluminum/polyester in contact with stranded tinned copper drain wire
Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
Jacket:
Low-lead Hypalon Cholorsulfonated Polyethylene (CSPE)/Elastomer blend
Options:
Bare copper conductor
Class C Stranding
Overall shielded pairs
Thermoplastic, Low-Smoke, Zero-Halogen (LSZH) jacket
In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
Other constructions available upon request
Approvals
Industry Compliances:
UL 13 Type PLTC
UL 1581
Flame Tests Compliances:
UL 1581 VW-1
IEEE 383
IEEE 1202
CSA FT-4
Other Compliances:
EPA 40 CFR, Part 261 for leachable lead content per TCLP
OSHA acceptable
Product Parameter
AWG Size |
Conductor Stranding |
No. of Pairs |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. (in) |
Approx LBS/MFT |
20 |
7/0.0121 |
2 |
0.012 |
0.04 |
0.34 |
54 |
20 |
7/0.0121 |
4 |
0.012 |
0.05 |
0.415 |
93 |
20 |
7/0.0121 |
8 |
0.012 |
0.05 |
0.525 |
157 |
20 |
7/0.0121 |
12 |
0.012 |
0.06 |
0.645 |
233 |
20 |
7/0.0121 |
16 |
0.012 |
0.06 |
0.715 |
294 |
20 |
7/0.0121 |
20 |
0.012 |
0.06 |
0.785 |
357 |
20 |
7/0.0121 |
24 |
0.012 |
0.07 |
0.875 |
422 |
20 |
7/0.0121 |
36 |
0.012 |
0.07 |
1.045 |
620 |
20 |
7/0.0121 |
50 |
0.012 |
0.07 |
1.215 |
828 |
18 |
7/0.0152 |
2 |
0.015 |
0.05 |
0.415 |
76 |
18 |
7/0.0152 |
4 |
0.015 |
0.05 |
0.475 |
113 |
18 |
7/0.0152 |
8 |
0.015 |
0.06 |
0.605 |
203 |
18 |
7/0.0152 |
12 |
0.015 |
0.06 |
0.75 |
300 |
18 |
7/0.0152 |
16 |
0.015 |
0.06 |
0.83 |
383 |
18 |
7/0.0152 |
20 |
0.015 |
0.07 |
0.945 |
483 |
18 |
7/0.0152 |
24 |
0.015 |
0.07 |
1.045 |
571 |
18 |
7/0.0152 |
36 |
0.015 |
0.07 |
1.225 |
816 |
18 |
7/0.0152 |
50 |
0.015 |
0.08 |
1.45 |
1119 |
16 |
7/0.0192 |
2 |
0.015 |
0.05 |
0.44 |
92 |
16 |
7/0.0192 |
4 |
0.015 |
0.05 |
0.545 |
163 |
16 |
7/0.0192 |
8 |
0.015 |
0.06 |
0.965 |
287 |
16 |
7/0.0192 |
12 |
0.015 |
0.06 |
0.885 |
437 |
16 |
7/0.0192 |
16 |
0.015 |
0.07 |
0.98 |
553 |
16 |
7/0.0192 |
20 |
0.015 |
0.07 |
1.08 |
680 |
16 |
7/0.0192 |
24 |
0.015 |
0.07 |
1.235 |
800 |
16 |
7/0.0192 |
36 |
0.015 |
0.08 |
1.405 |
1108 |
16 |
7/0.0192 |
50 |
0.015 |
0.08 |
1.64 |
1523 |
XLPE/PVC Instrumentation Cable with Overall Shielded Pairs/Triads
Applications:
Acceptable for use in free air or raceways in accordance with NEC
Typical applications include audio, intercom, control, energy management and alarm circuits.
In ducts, cable trays or conduit
In accordance with UL Subject 13 as Power-Limited Circuit Cable
In class 3 circuits in accordance with NEC
Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC
Construction:
Conductor:
18 AWG thru 16 AWG bare, annealed copper per ASTM B3
Class B stranding per ASTM B8
Insulation:
Flame-retardant Cross-linked Polyethylene (XPLE)
Color-coded per ICEA Method 1:
Pairs: Black and White
Triads: Black, White and Red
Shield:
Overall shielded pairs/triads
Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
Jacket:
Flame-retardant and sunlight-resistant Polyvinyl Chloride (PVC)
Options:
Tinned copper conductor
Class C Stranding
Individual and overall shielded pairs/triads
Ethylene Propylene Rubber (EPR) insulation
In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
Other constructions available upon request
Approvals:
Industry Compliances:
UL 13 Type PLTC
UL 1581
Flame Tests Compliances:
UL 1581 VW-1
IEEE 383
Other Compliances:
EPA 40 CFR, Part 261 for leachable lead content per TCLP
OSHA acceptable
Product Parameter
AWG Size |
Conductor Stranding |
No. of Pairs |
No. of Triads |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. (in) |
Approx LBS/MFT |
18 |
7/0.0152 |
1 |
|
0.015 |
0.035 |
0.235 |
32 |
18 |
7/0.0152 |
|
1 |
0.015 |
0.04 |
2.5 |
40 |
18 |
7/0.0152 |
2 |
|
0.015 |
0.04 |
0.365 |
56 |
18 |
7/0.0152 |
4 |
|
0.015 |
0.05 |
0.44 |
98 |
18 |
7/0.0152 |
8 |
|
0.015 |
0.05 |
0.55 |
175 |
18 |
7/0.0152 |
12 |
|
0.015 |
0.06 |
0.675 |
250 |
18 |
7/0.0152 |
16 |
|
0.015 |
0.06 |
0.75 |
317 |
18 |
7/0.0152 |
20 |
|
0.015 |
0.06 |
0.785 |
392 |
18 |
7/0.0152 |
24 |
|
0.015 |
0.06 |
0.905 |
476 |
18 |
7/0.0152 |
36 |
|
0.015 |
0.07 |
1.08 |
681 |
18 |
7/0.0152 |
50 |
|
0.015 |
0.07 |
1.245 |
913 |
16 |
7/0.0192 |
1 |
|
0.015 |
0.035 |
0.262 |
42 |
16 |
7/0.0192 |
|
1 |
0.015 |
0.04 |
0.28 |
53 |
16 |
7/0.0192 |
2 |
|
0.015 |
0.05 |
0.43 |
81 |
16 |
7/0.0192 |
4 |
|
0.015 |
0.05 |
0.49 |
131 |
16 |
7/0.0192 |
8 |
|
0.015 |
0.06 |
0.65 |
254 |
16 |
7/0.0192 |
12 |
|
0.015 |
0.06 |
0.755 |
350 |
16 |
7/0.0192 |
16 |
|
0.015 |
0.06 |
0.845 |
451 |
16 |
7/0.0192 |
20 |
|
0.015 |
0.07 |
0.88 |
545 |
16 |
7/0.0192 |
24 |
|
0.015 |
0.07 |
1.02 |
657 |
16 |
7/0.0192 |
36 |
|
0.015 |
0.07 |
1.22 |
965 |
16 |
7/0.0192 |
50 |
0.015 |
0.08 |
1.405 |
1322 |
XLPE/PVC Instrumentation Cable with Individual and Overall Shielded Pairs
Applications:
Acceptable for use in free air or raceways in accordance with NEC
Typical applications include audio, intercom, control, energy management and alarm circuits.
In ducts, cable trays or conduit
In accordance with UL Subject 13 as Power-Limited Circuit Cable
In class 3 circuits in accordance with NEC
Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC
Construction:
Conductor:
18 AWG thru 16 AWG bare, annealed copper per ASTM B3
Class B stranding per ASTM B8
Insulation:
Flame-retardant Cross-linked Polyethylene (XPLE)
Color-coded per ICEA Method 1:
Pairs: Black and White
Shield:
Individual and overall shielded pairs
Individual pairs are 100% shielded with Flexfoil aluminum/polyester in contact with stranded tinned copper drain wire
Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
Jacket:
Flame-retardant and sunlight-resistant Polyvinyl Chloride (PVC)
Options:
Tinned copper conductor
Class C Stranding
Overall shielded pairs
Ethylene Propylene Rubber (EPR) insulation
In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
Other constructions available upon request
Approvals:
Industry Compliances:
UL 13 Type PLTC
UL 1581
Flame Tests Compliances:
UL 1581 VW-1
IEEE 383
Other Compliances:
EPA 40 CFR, Part 261 for leachable lead content per TCLP
OSHA acceptable
Product Parameter
AWG Size |
Conductor Stranding |
No. of Pairs |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. (in) |
Approx LBS/MFT |
18 |
7/0.0152 |
2 |
0.015 |
0.05 |
0.41 |
73 |
18 |
7/0.0152 |
4 |
0.015 |
0.05 |
0.475 |
117 |
18 |
7/0.0152 |
8 |
0.015 |
0.05 |
0.605 |
215 |
18 |
7/0.0152 |
12 |
0.015 |
0.06 |
0.75 |
308 |
18 |
7/0.0152 |
16 |
0.015 |
0.06 |
0.83 |
392 |
18 |
7/0.0152 |
20 |
0.015 |
0.07 |
0.955 |
494 |
18 |
7/0.0152 |
24 |
0.015 |
0.07 |
1.03 |
583 |
18 |
7/0.0152 |
36 |
0.015 |
0.07 |
1.21 |
830 |
18 |
7/0.0152 |
50 |
0.015 |
0.08 |
1.425 |
1145 |
16 |
7/0.0152 |
2 |
0.015 |
0.05 |
0.41 |
73 |
16 |
7/0.0152 |
4 |
0.015 |
0.05 |
0.53 |
160 |
16 |
7/0.0152 |
8 |
0.015 |
0.06 |
0.71 |
293 |
16 |
7/0.0152 |
12 |
0.015 |
0.06 |
0.855 |
425 |
16 |
7/0.0152 |
16 |
0.015 |
0.07 |
0.955 |
563 |
16 |
7/0.0152 |
20 |
0.015 |
0.07 |
1.055 |
664 |
16 |
7/0.0152 |
24 |
0.015 |
0.07 |
1.16 |
780 |
16 |
7/0.0152 |
36 |
0.015 |
0.08 |
1.38 |
1137 |
16 |
7/0.0152 |
50 |
0.015 |
0.08 |
1.58 |
1518 |