| Industrial Cables | |||
Industrial Cables
Instrumentation Cable (600 Volt)
XLPE/HYP Instrumentation Cable with Individual and Overall Shielded Pairs/Triads
Applications:
Typical applications include audio, intercom, control, energy management and alarm circuits.
Acceptable for use in free air or raceways or direct burial
In wet or dry locations
Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC
XLPE/HYP Instrumentation Cable with Individual and Overall Shielded Pairs/Triads Features:
Rated at 90°C wet or dry
Ripcord applied to all cables with jacket thickness of 60 mils or less
Oil-resistant jacket
Sunlight and weather resistant
Excellent electrical, thermal, and physical properties
Excellent moisture resistance
Excellent flame resistance
"Heavy duty" rating per ICEA standards
Excellent low temperature cold bend characteristics
Meets cold bend test at -35°C
Construction:
Conductor:
18 AWG and 16 AWC tinned, annealed copper per ASTM B33
Class B stranding per ASTM B8
Insulation:
Flame-retardnat Cross-linked Polyethylene (XLPE)
Color-coded per ICEA Method 1:
Pairs: Black and White
Triads: Black, White and Red
Shield:
Individual and Overall shielded pairs/triads is aluminum/polyester in contact with stranded tinned copper drain wire
Jacket:
Low-lead Hypalon Cholorsulfonated Polyethylene (CSPE)/Elastomer blend
Options:
300V Type PLTC
Bare copper conductor
Class C Stranding
EHTC®-Ethylene Propylene Rubber jacket
Overall shielded pairs/traids
Thermoplasic, Low-Smoke, Zero-Halogen (LSZH) jacket
In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
Other constructions available upon request
Approvals:
Industry Compliances:
UL Type RFH-2, FFH-2 conductors
UL 1277 Type TC
UL 1581
ICEA S-82-552
ICEA S-73-532
Flame Tests Compliances:
UL 1581 VW-1
UL 1277
IEEE 383
IEEE 1202
CSA FT-4
ICEA T-29-520
Other Compliances:
EPA 40 CFR, Part 261 for leachable lead content per TCLP
OSHA acceptable
Product Parameter
AWG Size |
Conductor Stranding |
No. of Pairs |
No. of Triads |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. of Cable (in) |
Approx LBS/MFT |
18 |
7/0.0152 |
1 |
0.03 |
0.045 |
0.315 |
49 |
|
18 |
7/0.0152 |
1 |
0.03 |
0.045 |
0.335 |
64 |
|
18 |
7/0.0152 |
2 |
0.03 |
0.045 |
0.51 |
92 |
|
18 |
7/0.0152 |
4 |
0.03 |
0.06 |
0.63 |
167 |
|
18 |
7/0.0152 |
8 |
0.03 |
0.08 |
0.855 |
326 |
|
18 |
7/0.0152 |
12 |
0.03 |
0.08 |
1.03 |
441 |
|
18 |
7/0.0152 |
16 |
0.03 |
0.08 |
1.14 |
554 |
|
18 |
7/0.0152 |
20 |
0.03 |
0.08 |
1.265 |
676 |
|
18 |
7/0.0152 |
24 |
0.03 |
0.08 |
1.45 |
795 |
|
18 |
7/0.0152 |
36 |
0.03 |
0.11 |
1.65 |
1118 |
|
18 |
7/0.0152 |
50 |
0.03 |
0.11 |
2.085 |
1616 |
|
16 |
7/0.0192 |
1 |
0.03 |
0.045 |
0.345 |
61 |
|
16 |
7/0.0192 |
1 |
0.03 |
0.045 |
0.36 |
85 |
|
16 |
7/0.0192 |
2 |
0.03 |
0.06 |
0.585 |
130 |
|
16 |
7/0.0192 |
4 |
0.03 |
0.06 |
0.675 |
204 |
|
16 |
7/0.0192 |
8 |
0.03 |
0.08 |
0.915 |
394 |
|
16 |
7/0.0192 |
12 |
0.03 |
0.08 |
1.11 |
548 |
|
16 |
7/0.0192 |
16 |
0.03 |
0.08 |
1.35 |
713 |
|
16 |
7/0.0192 |
20 |
0.03 |
0.08 |
1.365 |
850 |
|
16 |
7/0.0192 |
24 |
0.03 |
0.08 |
1.57 |
1001 |
|
16 |
7/0.0192 |
36 |
0.03 |
0.11 |
1.98 |
1548 |
|
16 |
7/0.0192 |
50 |
0.03 |
0.11 |
2.165 |
2020 |
XLPE/Arctic-Grade PVC Instrumentation Cable with Overall Shielded Pairs/Triads
Applications:
Typical applications include industrial lighting, control and signaling circuits.
Primary installations cable trays, raceways or outdoor applications where supported by messenger wire
In wet or dry locations
XLPE/Arctic-Grade PVC Instrumentation Cable with Overall Shielded Pairs/Triads Features:
Rated at 90°C wet or dry
Ripcord applied to all cables with jacket thickness of 60 mils or less
Sunlight and weather resistant
Meets CSA cold impact test at -40°C
Meets ICEA and CSA cold bend test at -65°C
Construction:
Conductor:
18 AWG and 16 AWC tinned, annealed copper per ASTM B33
Class B stranding per ASTM B8
Insulation:
Flame-retardant Cross-Linked Polyethylene (XLPE)
Color-coded per ICEA Method 1:
Pairs: Black and White
Triads: Black, White and Red
Shield:
Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
Jacket:
Flame-retardant and sunlight-resistant Arctic-grade Polyvinyl Chloride (PVC)
Options:
Bare copper conductor
Class C Stranding
E-2 Color Code
CSA Rated TC for 14 AWG and larger
Other constructions available upon request
Approvals:
Industry Compliances:
UL 1277 Type TC
UL 1581
CSA C22.2 No. 239 Type CIC
Flame Tests Compliances:
UL 1581 VW-1
UL 1277
CSA FT-4
IEEE 383
Other Compliances:
EPA 40 CFR, Part 261 for leachable lead content per TCLP
OSHA acceptable
Product Parameter
AWG Size |
Conductor Stranding |
No. of Pairs |
No. of Triads |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. (in) |
Approx LBS/MFT |
18 |
7/0.0152 |
1 |
0.03 |
0.045 |
0.315 |
46 |
|
18 |
7/0.0152 |
1 |
0.03 |
0.045 |
0.34 |
57 |
|
18 |
7/0.0152 |
2 |
0.03 |
0.045 |
0.45 |
88 |
|
18 |
7/0.0152 |
4 |
0.03 |
0.045 |
0.56 |
144 |
|
18 |
7/0.0152 |
8 |
0.03 |
0.06 |
0.75 |
263 |
|
18 |
7/0.0152 |
12 |
0.03 |
0.08 |
0.85 |
358 |
|
18 |
7/0.0152 |
16 |
0.03 |
0.08 |
1.01 |
461 |
|
18 |
7/0.0152 |
20 |
0.03 |
0.08 |
1.085 |
600 |
|
18 |
7/0.0152 |
24 |
0.03 |
0.08 |
1.21 |
761 |
|
18 |
7/0.0152 |
36 |
0.03 |
0.08 |
1.5 |
1005 |
|
18 |
7/0.0152 |
50 |
0.03 |
0.08 |
2.57 |
1603 |
|
16 |
7/0.0192 |
1 |
0.03 |
0.045 |
0.345 |
32 |
|
16 |
7/0.0192 |
1 |
0.03 |
0.045 |
0.36 |
71 |
|
16 |
7/0.0192 |
2 |
0.03 |
0.045 |
0.56 |
121 |
|
16 |
7/0.0192 |
4 |
0.03 |
0.06 |
0.65 |
186 |
|
16 |
7/0.0192 |
8 |
0.03 |
0.06 |
0.81 |
324 |
|
16 |
7/0.0192 |
12 |
0.03 |
0.08 |
1 |
486 |
|
16 |
7/0.0192 |
16 |
0.03 |
0.08 |
1.12 |
616 |
|
16 |
7/0.0192 |
20 |
0.03 |
0.08 |
1.17 |
734 |
|
16 |
7/0.0192 |
24 |
0.03 |
0.08 |
1.44 |
894 |
|
16 |
7/0.0192 |
36 |
0.03 |
0.08 |
1.65 |
1254 |
|
16 |
7/0.0192 |
50 |
0.03 |
0.11 |
2.02 |
1800 |
XLPE/Arctic-Grade PVC Instrumentation Cable with Individual and Overall Shielded Pairs
Applications:
Typical applications include industrial lighting, control and signaling circuits.
Primary installations cable trays, raceways or outdoor applications where supported by messenger wire
In wet or dry locations
Features:
Rated at 90°C wet or dry
Ripcord applied to all cables with jacket thickness of 60 mils or less
Sunlight and weather resistant
Meets CSA cold impact test at -40°C
Meets ICEA and CSA cold bend test at -65°C
Construction:
Conductor:
18 AWG and 16 AWC tinned, annealed copper per ASTM B33
Class B stranding per ASTM B8
Insulation:
Flame-retardant Cross-Linked Polyethylene (XLPE)
Color-coded per ICEA Method 1:
Pairs: Black and White
Shield:
Individual pairs are 100% shielded with aluminum/polyester in contact with stranded tinned copper drain wire
Jacket:
Flame-retardant and sunlight-resistant Arctic-grade Polyvinyl Chloride (PVC)
Options:
Bare copper conductor
Class C Stranding
E-2 Color Code
CSA Rated TC for 14 AWG and larger
Other constructions available upon request
Approvals:
Industry Compliances:
UL 1277 Type TC
UL 1581
CSA C22.2 No. 239 Type CIC
Flame Tests Compliances:
UL 1581 VW-1
UL 1277
CSA FT-4
IEEE 383
Other Compliances:
EPA 40 CFR, Part 261 for leachable lead content per TCLP
OSHA acceptable
Product Parameter
AWG Size |
Conductor Stranding |
No. of Pairs |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. of Cable (in) |
Approx LBS/MFT |
18 |
7/0.0152 |
2 |
0.03 |
0.06 |
0.595 |
42 |
18 |
7/0.0152 |
4 |
0.03 |
0.06 |
0.695 |
80 |
18 |
7/0.0152 |
8 |
0.03 |
0.06 |
0.9 |
155 |
18 |
7/0.0152 |
12 |
0.03 |
0.08 |
1.11 |
230 |
18 |
7/0.0152 |
16 |
0.03 |
0.08 |
1.26 |
306 |
18 |
7/0.0152 |
20 |
0.03 |
0.08 |
1.315 |
375 |
18 |
7/0.0152 |
24 |
0.03 |
0.08 |
1.51 |
456 |
18 |
7/0.0152 |
36 |
0.03 |
0.11 |
1.82 |
674 |
18 |
7/0.0152 |
50 |
0.03 |
0.11 |
2.095 |
946 |
16 |
7/0.0192 |
2 |
0.03 |
0.06 |
0.595 |
132 |
16 |
7/0.0192 |
4 |
0.03 |
0.06 |
0.695 |
212 |
16 |
7/0.0192 |
8 |
0.03 |
0.06 |
0.9 |
395 |
16 |
7/0.0192 |
12 |
0.03 |
0.08 |
1.11 |
578 |
16 |
7/0.0192 |
16 |
0.03 |
0.08 |
1.26 |
733 |
16 |
7/0.0192 |
20 |
0.03 |
0.08 |
1.315 |
845 |
16 |
7/0.0192 |
24 |
0.03 |
0.08 |
1.51 |
1009 |
16 |
7/0.0192 |
36 |
0.03 |
0.11 |
1.82 |
1259 |
16 |
7/0.0192 |
50 |
0.03 |
0.11 |
2.095 |
2032 |
XLPE/PVC Instrumentation Cable with Overall Shielded Pairs/Triads
Applications:
In free air, raceways or direct burial
In wet or dry locations
Permitted for use in Class I Division 2 Industrial hazardous locations per NEC
Features:
Rated at 90°C wet or dry
Ripcord applied to all cables with jacket thickness of 60 mils or less
Abrasion- and chemical-resistant
Sunlight and weather resistant
Excellent electrical properties
Meets cold bend test at -25°C
Construction:
Conductor:
18 AWG and 16 AWC bare, annealed copper per ASTM B3
Class B stranding per ASTM B8
Insulation:
Flame-retardant Cross-Linked Polyethylene (XLPE)
Color-coded per ICEA Method 1:
Pairs: Black and White
Triads: Black, White and Red
Shield:
Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
Jacket:
Flame-retardant and sunlight-resistant Arctic-grade Polyvinyl Chloride (PVC)
Options:
300V Type PLTC
Tinned copper conductor
Class C Stranding
Individual and overall shielded pairs/triads
EVTC-Ethylene Propylene Rubber (EPR) insulation
Other constructions available upon request
Approvals:
Industry Compliances:
UL 1277 Type TC
UL 1581
ICEA S-82-552
ICEA S-73-532
Flame Tests Compliances:
UL 1581 VW-1
UL 1277
IEEE 383
IEEE 1202
CSA FT-4
Other Compliances:
EPA 40 CFR, Part 261 for leachable lead content per TCLP
OSHA acceptable
Product Parameter
AWG Size |
Conductor Stranding |
No. of Pairs |
No. of Triads |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. (in) |
Approx LBS/MFT |
18 |
7/0.0152 |
1 |
0.03 |
0.045 |
0.315 |
46 |
|
18 |
7/0.0152 |
1 |
0.03 |
0.045 |
0.34 |
58 |
|
18 |
7/0.0152 |
2 |
0.03 |
0.045 |
0.45 |
88 |
|
18 |
7/0.0152 |
4 |
0.03 |
0.045 |
0.56 |
144 |
|
18 |
7/0.0152 |
8 |
0.03 |
0.06 |
0.75 |
263 |
|
18 |
7/0.0152 |
12 |
0.03 |
0.08 |
0.85 |
358 |
|
18 |
7/0.0152 |
16 |
0.03 |
0.08 |
1.01 |
461 |
|
18 |
7/0.0152 |
20 |
0.03 |
0.08 |
1.085 |
600 |
|
18 |
7/0.0152 |
24 |
0.03 |
0.08 |
1.21 |
701 |
|
18 |
7/0.0152 |
36 |
0.03 |
0.08 |
1.5 |
1005 |
|
18 |
7/0.0152 |
50 |
0.03 |
0.08 |
2.57 |
1603 |
|
16 |
7/0.0192 |
1 |
0.03 |
0.045 |
0.345 |
32 |
|
16 |
7/0.0192 |
1 |
0.03 |
0.045 |
0.36 |
72 |
|
16 |
7/0.0192 |
2 |
0.03 |
0.045 |
0.56 |
121 |
|
16 |
7/0.0192 |
4 |
0.03 |
0.06 |
0.65 |
186 |
|
16 |
7/0.0192 |
8 |
0.03 |
0.06 |
0.81 |
324 |
|
16 |
7/0.0192 |
12 |
0.03 |
0.08 |
1 |
486 |
|
16 |
7/0.0192 |
16 |
0.03 |
0.08 |
1.12 |
616 |
|
16 |
7/0.0192 |
20 |
0.03 |
0.08 |
1.17 |
734 |
|
16 |
7/0.0192 |
24 |
0.03 |
0.08 |
1.44 |
894 |
|
16 |
7/0.0192 |
36 |
0.03 |
0.08 |
1.65 |
1254 |
|
16 |
7/0.0192 |
50 |
0.03 |
0.11 |
2.02 |
1800 |
XLPE/PVC Instrumentation Cable with Individual and Overall Shielded Pairs
Applications:
In free air, raceways or direct burial
In wet or dry locations
Permitted for use in Class I Division 2 Industrial hazardous locations per NEC
Features:
Rated at 90°C wet or dry
Ripcord applied to all cables with jacket thickness of 60 mils or less
Abrasion- and chemical-resistant
Sunlight and weather resistant
Excellent electrical properties
Meets cold bend test at -25°C
Construction:
Conductor:
18 AWG and 16 AWC bare, annealed copper per ASTM B3
Class B stranding per ASTM B8
Insulation:
Flame-retardant Cross-Linked Polyethylene (XLPE)
Color-coded per ICEA Method 1:
Pairs: Black and White
Shield:
Individual and Overall shields are aluminum/polyester in contact with stranded tinned copper drain wire
Jacket:
Flame-retardant and sunlight-resistant Arctic-grade Polyvinyl Chloride (PVC)
Options:
300V Type PLTC
Tinned copper conductor
Class C Stranding
Overall shielded pairs/triads
EVTC-Ethylene Propylene Rubber (EPR) insulation
Other constructions available upon request
Approvals:
Industry Compliances:
UL 1277 Type TC
UL 1581
ICEA S-82-552
ICEA S-73-532
Flame Tests Compliances:
UL 1581 VW-1
UL 1277
IEEE 383
IEEE 1202
CSA FT-4
Other Compliances:
EPA 40 CFR, Part 261 for leachable lead content per TCLP
OSHA acceptable
Product Parameter
AWG Size |
Conductor Stranding |
No. of Pairs |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. (in) |
Approx LBS/MFT |
18 |
7/0.0152 |
2 |
0.03 |
0.045 |
0.515 |
95 |
18 |
7/0.0152 |
4 |
0.03 |
0.06 |
0.625 |
170 |
18 |
7/0.0152 |
8 |
0.03 |
0.06 |
0.805 |
292 |
18 |
7/0.0152 |
12 |
0.03 |
0.08 |
1.02 |
442 |
18 |
7/0.0152 |
16 |
0.03 |
0.08 |
1.13 |
554 |
18 |
7/0.0152 |
20 |
0.03 |
0.08 |
1.235 |
666 |
18 |
7/0.0152 |
24 |
0.03 |
0.08 |
1.465 |
802 |
18 |
7/0.0152 |
36 |
0.03 |
0.08 |
1.63 |
1116 |
18 |
7/0.0152 |
50 |
0.03 |
0.11 |
1.975 |
1598 |
16 |
7/0.0192 |
2 |
0.03 |
0.06 |
0.595 |
135 |
16 |
7/0.0192 |
4 |
0.03 |
0.06 |
0.695 |
214 |
16 |
7/0.0192 |
8 |
0.03 |
0.06 |
0.9 |
399 |
16 |
7/0.0192 |
12 |
0.03 |
0.08 |
1.11 |
584 |
16 |
7/0.0192 |
16 |
0.03 |
0.08 |
1.26 |
712 |
16 |
7/0.0192 |
20 |
0.03 |
0.08 |
1.315 |
845 |
16 |
7/0.0192 |
24 |
0.03 |
0.08 |
1.51 |
1009 |
16 |
7/0.0192 |
36 |
0.03 |
0.11 |
1.82 |
1259 |
16 |
7/0.0192 |
50 |
0.03 |
0.11 |
2.095 |
2032 |
Nuclear SIS Wire (IEEE 383-1974)
Applications:
SIS wire is 600V flexible single conductor, insulated, Class 1E rated
For use in Class 1E low voltage applications in operation and interconnection of protective devices where optimum performance is required.
Nuclear SIS Wire Features:
Rated at 90°C
Fully traceable
Qualified for 40-year service life
Radiation resistant (up to 200 megarads)
Long-term thermal endurance and superior electricals
Excellent mechanical cut through properties
Long-term moisture and radiation stability
Free stripping for ease of termination
Factory rework for service in nuclear power generating stations
Construction:
Conductor:
18 AWG and 10 AWG tinned, annealed copper per ASTM B33; Class K stranding per ASTM B174
8 AWG thru 1000 kcmil tinned, annealed copper per ASTM B33; Class H stranding per ASTM B173
Insulation:
Nucular SIS Wire is flame-retardant, heat, moisture and radiation resistant, thermoset Cross-Linked Polyethylene (FR-XLPE)
Color Code: Gray
Options:
Conductor Stranding
Bare Copper
Full-colored insulation
UL listed SIS/XHHW for sizes 14 AWG thru 4/0 AWG
UL listed XHHW for kcmil sizes
Approvals:
Industry Compliances:
Class 1E Qualified in accordance with IEEE 323-1974 and IEEE 383-1974
ANSI N45.2
ICEA S-95-658 (Formerly ICEA S-66-524 & S-19-81)
Flame Tests Compliances:
IEEE 383 (70,000 BTU/hr)
ICEA T-29-520 (210,000 BTU/hr)
UL VW-1
Other Compliances:
Quality assurance program in accordance with NRC 10CFR50 Appendix B
ASME NQA-1:2000
NUPIC
Product Parameter
AWG Size |
Conductor Stranding |
Nom. Insul. Thick. (in) |
Nom. O.D. (in) |
Approx LBS/MFT |
18 |
16/0.010 |
0.03 |
0.108 |
9 |
16 |
26/0.010 |
0.03 |
0.119 |
13 |
14 |
41/0.010 |
0.03 |
0.133 |
18 |
12 |
65/0.010 |
0.03 |
0.15 |
27 |
10 |
105/0.010 |
0.03 |
0.174 |
41 |
8 |
133/0.0111 |
0.045 |
0.257 |
70 |
6 |
133/0.0140 |
0.045 |
0.299 |
105 |
4 |
133/0.0177 |
0.045 |
0.353 |
160 |
2 |
133/0.0223 |
0.045 |
0.42 |
244 |
1 |
259/0.0180 |
0.055 |
0.476 |
312 |
1/0 |
259/0.0202 |
0.055 |
0.52 |
386 |
2/0 |
259/0.0227 |
0.055 |
0.571 |
481 |
3/0 |
259/0.0255 |
0.055 |
0.628 |
600 |
4/0 |
259/0.0286 |
0.055 |
0.714 |
746 |
250 |
427/0.0242 |
0.065 |
0.761 |
888 |
350 |
427/0.0286 |
0.065 |
0.874 |
1221 |
500 |
427/0.0342 |
0.065 |
1.034 |
1728 |
750 |
703/0.0327 |
0.08 |
1.286 |
2611 |
1000 |
703/0.0377 |
0.08 |
1.458 |
3441 |