| Industrial Cables | |||
Industrial Cables
Multi-Conductor Control Cable and Power Cable (600 Volt)
XLPE/HYP Unshielded Control Cable with Printed Numbers (Type TC)
Applications:
In free air, raceways or direct burial
In wet or dry locations
Permitted for use in Class I, Div 2 industrial hazardous locations per NEC Article 501 and Class 1 circuits per NEC
Features:
Rated at 90°C, wet or dry
Ripcord applied to all cables with jacket thickness of 60 mils or less
Excellent physical, thermal and electrical properties
Excellent moisture resistance
Outstanding resistance to crush, compression cuts and heat deformation
Excellent flame resistance
Oil resistant jacket
"Heavy Duty" rating per ICEA standards
Sunlight and weather resistant
Excellent low temperature cold bend characteristics
Meets cold bend test at -35°C
Construction:
Conductor:
16 AWG thru 10 AWG fully annealed stranded tinned copper per ASTM B33
Class B stranding per ASTM B8
Insulation:
Flame retardant Cross-Linked Polyethylene (XLPE)
Color coded per ICEA Method 1; Table E-2 plus alpha-numeric printed numbers (Does not include white or green
Jacket:
Low-lead Hypalon® Chlorosulfonated Polyethylene (CSPE)/Elastomer blend
XLPE/HYP Unshielded Control Cable with Printed Numbers (Type TC) Options:
2kV version
Bare copper conductor
Class C stranding
Overall shielded multi conductor
Ethylene Propylene Rubber (EPR) insulation
Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket
Flame retardant, Polyvinyl Chloride (PVC) jacket
Other constructions available upon request
Approvals:
Industry Approvals
UL 44 Type XHHW-2
UL 1277 Type TC
UL 1581
ICEA S-73-532
ICEA S-95-658/NEMA WC74
Flame Tests Compliances:
UL 1581 VW-1
UL 1277
IEEE 383
IEEE 1202
CSA FT4
ICEA T-29-520
Other Compliances:
Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
OSHA acceptable
Product Parameter
AWG Size |
No. of Cond. |
Conductor Stranding |
Nom. O.D. (in) |
Nom. Insul. Thick. (in) |
Jacket Thick |
Approx Dimension |
Approx LBS/MFT |
16 |
2 |
7/0.0192 |
0.34 |
0.03 |
0.045 |
61 |
|
16 |
3 |
7/0.0192 |
0.36 |
0.03 |
0.045 |
73 |
|
16 |
4 |
7/0.0192 |
0.39 |
0.03 |
0.045 |
91 |
|
16 |
5 |
7/0.0192 |
0.42 |
0.03 |
0.045 |
110 |
|
16 |
7 |
7/0.0192 |
0.46 |
0.03 |
0.045 |
141 |
|
16 |
9 |
7/0.0192 |
0.565 |
0.03 |
0.06 |
199 |
|
14 |
2 |
19/0.0242 |
0.03 |
0.045 |
.230 x .365 |
68 |
|
14 |
2 |
19/0.0242 |
0.37 |
0.03 |
0.045 |
75 |
|
14 |
3 |
19/0.0242 |
0.39 |
0.03 |
0.045 |
95 |
|
14 |
4 |
19/0.0242 |
0.425 |
0.03 |
0.045 |
118 |
|
14 |
5 |
19/0.0242 |
0.465 |
0.03 |
0.045 |
143 |
|
14 |
7 |
19/0.0242 |
0.505 |
0.03 |
0.045 |
179 |
|
14 |
9 |
19/0.0242 |
0.62 |
0.03 |
0.06 |
249 |
|
14 |
12 |
19/0.0242 |
0.7 |
0.03 |
0.06 |
317 |
|
14 |
19 |
19/0.0242 |
0.815 |
0.03 |
0.06 |
467 |
|
14 |
37 |
19/0.0242 |
1.13 |
0.03 |
0.08 |
899 |
|
12 |
2 |
19/0.0305 |
0.03 |
0.045 |
.250 x .400 |
85 |
|
12 |
2 |
19/0.0305 |
0.41 |
0.03 |
0.045 |
98 |
|
12 |
3 |
19/0.0305 |
0.435 |
0.03 |
0.045 |
127 |
|
12 |
4 |
19/0.0305 |
0.475 |
0.03 |
0.045 |
160 |
|
12 |
5 |
19/0.0305 |
0.52 |
0.03 |
0.045 |
194 |
|
12 |
7 |
19/0.0305 |
0.595 |
0.03 |
0.06 |
264 |
|
12 |
9 |
19/0.0305 |
0.695 |
0.03 |
0.06 |
345 |
|
12 |
12 |
19/0.0305 |
0.78 |
0.03 |
0.06 |
435 |
|
12 |
19 |
19/0.0305 |
0.955 |
0.03 |
0.08 |
690 |
|
12 |
37 |
19/0.0305 |
1.265 |
0.03 |
0.08 |
1393 |
|
10 |
2 |
7/0.0385 |
0.03 |
0.045 |
.270 x .445 |
117 |
|
10 |
2 |
7/0.0385 |
0.455 |
0.03 |
0.045 |
126 |
|
10 |
3 |
7/0.0385 |
0.485 |
0.03 |
0.045 |
176 |
|
10 |
4 |
7/0.0385 |
0.56 |
0.03 |
0.06 |
240 |
|
10 |
5 |
7/0.0385 |
0.615 |
0.03 |
0.06 |
291 |
|
10 |
7 |
7/0.0385 |
0.67 |
0.03 |
0.06 |
376 |
|
10 |
9 |
7/0.0385 |
0.765 |
0.03 |
0.06 |
456 |
|
10 |
12 |
7/0.0385 |
0.905 |
0.03 |
0.08 |
636 |
XLPE/HYP Unshielded Control Cable (Type TC)
Applications:
In free air, raceways or direct burial
In wet or dry locations
Permitted for use in Class I, Div 2 industrial hazardous locations per NEC Article 501 and Class 1 circuits per NEC
Features:
Rated at 90°C, wet or dry
Ripcord applied to all cables with jacket thickness of 60 mils or less
Excellent physical, thermal and electrical properties
Excellent moisture resistance
Outstanding resistance to crush, compression cuts and heat deformation
Excellent flame resistance
Oil resistant jacket
"Heavy Duty" rating per ICEA standards
Sunlight and weather resistant
Excellent low temperature cold bend characteristics
Meets cold bend test at -35°C
Construction:
Conductor:
14 AWG thru 10 AWG fully annealed stranded tinned copper per ASTM B33
Class B stranding per ASTM B8
Insulation:
Flame retardant Cross-Linked Polyethylene (XLPE)
Color coded per ICEA Method 1; Table E-1
Jacket:
Low-lead Hypalon® Chlorosulfonated Polyethylene (CSPE)/Elastomer blend
XLPE/HYP Unshielded Control Cable (Type TC) Options:
2kV version
Bare copper conductor
Class C stranding
Overall shielded multi conductor
Ethylene Propylene Rubber (EPR) insulation
Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket
Flame retardant, Polyvinyl Chloride (PVC) jacket
Other constructions available upon request
Approvals
UL 44 Type XHHW-2
UL 1277 Type TC
UL 1581
ICEA S-73-532
ICEA S-95-658/NEMA WC74
Flame Tests Compliances:
UL 1581 VW-1
UL 1277
IEEE 383
IEEE 1202
CSA FT4
ICEA T-29-520
Other Compliances:
Meeets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
OSHA acceptable
Product Parameter
AWG Size |
No. of Cond. |
Conductor Stranding |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. (in) |
Approx Dimension |
Approx LBS/MFT |
14 |
2 |
19/0.0242 |
0.03 |
0.045 |
.230 x .365 |
68 |
|
14 |
2 |
19/0.0242 |
0.03 |
0.045 |
0.37 |
75 |
|
14 |
3 |
19/0.0242 |
0.03 |
0.045 |
0.39 |
95 |
|
14 |
4 |
19/0.0242 |
0.03 |
0.045 |
0.425 |
118 |
|
14 |
5 |
19/0.0242 |
0.03 |
0.045 |
0.465 |
143 |
|
14 |
7 |
19/0.0242 |
0.03 |
0.045 |
0.505 |
179 |
|
14 |
9 |
19/0.0242 |
0.03 |
0.06 |
0.62 |
249 |
|
14 |
12 |
19/0.0242 |
0.03 |
0.06 |
0.7 |
317 |
|
14 |
19 |
19/0.0242 |
0.03 |
0.06 |
0.815 |
467 |
|
14 |
25 |
19/0.0242 |
0.03 |
0.08 |
1 |
632 |
|
14 |
30 |
19/0.0242 |
0.03 |
0.08 |
1.05 |
731 |
|
14 |
37 |
19/0.0242 |
0.03 |
0.08 |
1.13 |
899 |
|
12 |
2 |
7/0.0385 |
0.03 |
0.045 |
.250 x .400 |
85 |
|
12 |
2 |
7/0.0385 |
0.03 |
0.045 |
0.41 |
98 |
|
12 |
3 |
7/0.0385 |
0.03 |
0.045 |
0.435 |
127 |
|
12 |
4 |
7/0.0385 |
0.03 |
0.045 |
0.475 |
160 |
|
12 |
5 |
7/0.0385 |
0.03 |
0.045 |
0.52 |
194 |
|
12 |
7 |
7/0.0385 |
0.03 |
0.06 |
0.595 |
264 |
|
12 |
9 |
7/0.0385 |
0.03 |
0.06 |
0.695 |
345 |
|
12 |
12 |
7/0.0385 |
0.03 |
0.06 |
0.78 |
435 |
|
12 |
19 |
7/0.0385 |
0.03 |
0.08 |
0.955 |
690 |
|
12 |
25 |
7/0.0385 |
0.03 |
0.08 |
1.095 |
858 |
|
12 |
30 |
7/0.0385 |
0.03 |
0.08 |
1.175 |
997 |
|
12 |
37 |
7/0.0385 |
0.03 |
0.08 |
1.265 |
1393 |
|
10 |
2 |
19/0.0305 |
0.03 |
0.045 |
.270 x .445 |
117 |
|
10 |
2 |
19/0.0305 |
0.03 |
0.045 |
0.455 |
126 |
|
10 |
3 |
19/0.0305 |
0.03 |
0.045 |
0.485 |
176 |
|
10 |
4 |
19/0.0305 |
0.03 |
0.06 |
0.56 |
240 |
|
10 |
5 |
19/0.0305 |
0.03 |
0.06 |
0.615 |
291 |
|
10 |
7 |
19/0.0305 |
0.03 |
0.06 |
0.67 |
376 |
|
10 |
9 |
19/0.0305 |
0.03 |
0.06 |
0.765 |
456 |
|
10 |
12 |
19/0.0305 |
0.03 |
0.08 |
0.905 |
636 |
XLPE/HYP Low-Voltage Unshielded Power Cable (Type TC-ER)
Applications:
In free air, raceways or direct burial
In wet or dry locations
Permitted for Exposed Run 'ER' use in accordance with NEC for 2 AWG and larger
Permitted for use in Class I, Div 2 industrial hazardous locations per NEC
XLPE/HYP Low-Voltage Unshielded Power Cable (Type TC-ER) Features:
Rated at 90°C, wet or dry
Ripcord applied to all cables with jacket thickness of 60 mils or less
Excellent physical, thermal and electrical properties
Excellent moisture resistance
Outstanding resistance to crush, compression cuts and heat deformation
Excellent flame resistance
Oil resistant jacket
"Heavy Duty" rating per ICEA standards
Sunlight and weather resistant
Excellent low temperature cold bend characteristics
Meets cold bend test at -35°C
Meets the crush and impact requirements of Type MC cable for 2 AWG and larger
Construction:
Conductor:
14 AWG thru 500 kcmil tinned, annealed copper per ASTM B33
Class B stranding per ASTM B8
Insulation:
Flame retardant Cross-Linked Polyethylene (XLPE)
Color coded per ICEA Method 4; Individual conductors colored black with conductor number surface printed in contrasting ink
Ground:
Uninsulated tinned annealed copper per ASTM B3
Class B stranding per ASTM B8
Jacket:
Low-lead Hypalon® Chlorosulfonated Polyethylene (CSPE)/Elastomer blend
XLPE/HYP Low-Voltage Unshielded Power Cable (Type TC-ER) Options:
2kV version
Bare copper conductor
Class C stranding
Overall shielded multi conductor
Insulated ground conductor
Flame retardant Ethylene Propylene Rubber (EPR) insulation
Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket
Other constructions available upon request
Approvals:
Industry Approvals
UL 44 Type XHHW-2
UL 1277 Type TC-ER for 2 AWG and larger
UL 1581
ICEA S-73-532
ICEA S-95-658/NEMA WC70
Flame Tests Compliances:
UL 1581 VW-1
UL 1277
IEEE 383
IEEE 1202
CSA FT4
ICEA T-29-520
Other Compliances:
Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
OSHA acceptable
Product Parameter
AWG Size |
No. of Cond. |
Conductor Stranding |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. (in) |
Ground AWG Size |
Approx LBS/MFT |
14 |
3 |
19/0.0242 |
0.03 |
0.045 |
0.425 |
14 |
118 |
12 |
3 |
19/0.0305 |
0.03 |
0.045 |
0.475 |
12 |
160 |
10 |
3 |
7/0.0385 |
0.03 |
0.06 |
0.526 |
10 |
240 |
8 |
3 |
7/0.0486 |
0.045 |
0.06 |
0.66 |
10 |
223 |
8 |
4 |
7/0.0486 |
0.045 |
0.06 |
0.725 |
10 |
421 |
6 |
3 |
7/0.0612 |
0.045 |
0.06 |
0.745 |
8 |
481 |
6 |
4 |
7/0.0612 |
0.045 |
0.06 |
0.82 |
8 |
600 |
4 |
3 |
7/0.0772 |
0.045 |
0.08 |
0.89 |
8 |
702 |
4 |
4 |
7/0.0772 |
0.045 |
0.08 |
0.975 |
8 |
882 |
2 |
3 |
7/0.0974 |
0.045 |
0.08 |
1.02 |
6 |
1024 |
2 |
4 |
7/0.0974 |
0.045 |
0.08 |
1.12 |
6 |
1295 |
1 |
3 |
19/0.0664 |
0.055 |
0.08 |
1.12 |
6 |
1199 |
1 |
4 |
19/0.0664 |
0.055 |
0.08 |
1.235 |
6 |
1704 |
1/0 |
3 |
19/0.0745 |
0.055 |
0.08 |
1.24 |
6 |
1505 |
1/0 |
4 |
19/0.0745 |
0.055 |
0.08 |
1.33 |
6 |
1830 |
2/0 |
3 |
19/0.0837 |
0.055 |
0.08 |
1.34 |
6 |
1810 |
2/0 |
4 |
19/0.0837 |
0.055 |
0.08 |
1.48 |
6 |
2326 |
3/0 |
3 |
19/0.0940 |
0.055 |
0.08 |
1.42 |
4 |
2437 |
3/0 |
4 |
19/0.0940 |
0.055 |
0.08 |
1.57 |
4 |
3123 |
4/0 |
3 |
19/0.1055 |
0.055 |
0.08 |
1.575 |
4 |
2725 |
4/0 |
4 |
19/0.1055 |
0.055 |
0.11 |
1.765 |
4 |
3909 |
250 |
3 |
37/0.0822 |
0.065 |
0.11 |
1.755 |
4 |
3605 |
250 |
4 |
37/0.0822 |
0.065 |
0.11 |
1.935 |
4 |
4571 |
350 |
3 |
37/0.0973 |
0.065 |
0.11 |
2.01 |
3 |
4423 |
350 |
4 |
37/0.0973 |
0.065 |
0.11 |
2.18 |
4 |
6068 |
500 |
3 |
37/0.1162 |
0.065 |
0.11 |
2.305 |
2 |
6097 |
500 |
4 |
37/0.1162 |
0.065 |
0.11 |
2.555 |
2 |
7905 |
XLPE/PVC Unshielded Control Cable
Applications:
In free air, raceways and direct burial
In wet or dry locations
Approved for direct burial, Class I, Div 2 industrial hazardous locations per NEC
Permitted for Exposed Run 'ER' use in accordance with NEC for 3 or more conductors
XLPE/PVC Unshielded Control Cable Features:
Rated at 90°C wet or dry
Ripcord applied to all cables with jacket thickness of 60 mils or less
Excellent electrical properties
Abrasion and chemical resistant
Sunlight and weather resistant
Meets ICEA and CSA cold bend test at -25°C
Meets the crush and impact requirements of Type MC
Construction:
Conductor:
14 AWG thru 10 AWG fully annealed stranded bare copper per ASTM B3
Class B stranding per ASTM B8
Insulation:
Flame retardant Cross-Linked Polyethylene (XLPE)
Color-coded per ICEA Method 1; Table E-2 Does not include white or green
Jacket:
Flame retardant and sunlight resistant Polyvinyl Chloride (PVC)
XLPE/PVC Unshielded Control Cable Options:
Tinned copper conductor
Class C stranding
E-1 Color Code
Overall shielded multi conductors
Ethylene Propylene Rubber (EPR) insulation
Low-lead Hypalon Chlorosulfonated Polyethylene (CSPE) / Elastomer blend
Insulated or uninsulated ground conductor
Other constructions available upon request
Approvals:
Industry Approvals
UL 44 Type XHHW-2
UL 1277 Type TC-ER for 3 or more conductors
UL 1581
ICEA S-73-532
ICEA S-95-658/NEMA WC70
Flame Tests Approvals
UL 1581 VW-1
UL 1277
IEEE 383
IEEE 1202
CSA FT4
Other Compliances:
Meeets EPA 10 CFR, Part 261 for leachable lead content per TCLP method
OSHA acceptable
Product Parameter
AWG Size |
No. of Cond. |
Conductor Stranding |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. (in) |
Approx Dimension |
Ground AWG Size |
Approx LBS/MFT |
14 |
2 |
19/0.0242 |
0.03 |
0.045 |
.235 x .370 |
62 |
||
14 |
2 |
19/0.0242 |
0.03 |
0.045 |
0.365 |
73 |
||
14 |
3 |
19/0.0242 |
0.03 |
0.045 |
0.39 |
93 |
||
14 |
4 |
19/0.0242 |
0.03 |
0.045 |
0.425 |
116 |
||
14 |
5 |
19/0.0242 |
0.03 |
0.045 |
0.465 |
140 |
||
14 |
7 |
19/0.0242 |
0.03 |
0.045 |
0.59 |
176 |
||
14 |
9 |
19/0.0242 |
0.03 |
0.06 |
0.62 |
245 |
||
14 |
12 |
19/0.0242 |
0.03 |
0.06 |
0.68 |
302 |
||
14 |
19 |
19/0.0242 |
0.03 |
0.06 |
0.8 |
460 |
||
14 |
25 |
19/0.0242 |
0.03 |
0.08 |
0.985 |
641 |
||
14 |
30 |
19/0.0242 |
0.03 |
0.08 |
1.05 |
740 |
||
14 |
37 |
19/0.0242 |
0.03 |
0.08 |
1.13 |
888 |
||
12 |
2 |
19/0.0305 |
0.03 |
0.045 |
.245 x 400 |
86 |
||
12 |
2 |
19/0.0305 |
0.03 |
0.045 |
0.41 |
96 |
||
12 |
3 |
19/0.0305 |
0.03 |
0.045 |
0.435 |
12 |
143 |
|
12 |
3 |
19/0.0305 |
0.03 |
0.045 |
0.135 |
125 |
||
12 |
4 |
19/0.0305 |
0.03 |
0.045 |
0.475 |
157 |
||
12 |
5 |
19/0.0305 |
0.03 |
0.045 |
0.515 |
191 |
||
12 |
7 |
19/0.0305 |
0.03 |
0.06 |
0.595 |
260 |
||
12 |
9 |
19/0.0305 |
0.03 |
0.06 |
0.695 |
340 |
||
12 |
12 |
19/0.0305 |
0.03 |
0.06 |
0.78 |
429 |
||
12 |
19 |
19/0.0305 |
0.03 |
0.08 |
0.93 |
681 |
||
12 |
25 |
19/0.0305 |
0.03 |
0.08 |
1.095 |
885 |
||
12 |
30 |
19/0.0305 |
0.03 |
0.08 |
1.15 |
1005 |
||
12 |
37 |
19/0.0305 |
0.03 |
0.08 |
1.24 |
1185 |
||
10 |
2 |
7/0.0385 |
0.03 |
0.045 |
.290 x .480 |
114 |
||
10 |
2 |
7/0.0385 |
0.03 |
0.045 |
0.455 |
130 |
||
10 |
3 |
7/0.0385 |
0.03 |
0.045 |
0.485 |
10 |
201 |
|
10 |
3 |
7/0.0385 |
0.03 |
0.045 |
0.485 |
173 |
||
10 |
4 |
7/0.0385 |
0.03 |
0.06 |
0.515 |
236 |
||
10 |
5 |
7/0.0385 |
0.03 |
0.06 |
0.615 |
287 |
||
10 |
7 |
7/0.0385 |
0.03 |
0.06 |
0.67 |
371 |
||
10 |
9 |
7/0.0385 |
0.03 |
0.06 |
0.785 |
479 |
||
10 |
12 |
7/0.0385 |
0.03 |
0.08 |
0.895 |
644 |
XLPE/PVC Unshielded Low-Voltage Power Cable
Applications:
In free air, raceways and direct burial
In wet or dry locations
Permitted for use in Class I, Div 2 industrial hazardous locations per NEC
Permitted for Exposed Run 'ER' use in accordance with NEC
XLPE/PVC Unshielded Low-Voltage Power Cable Features:
Rated at 90°C wet or dry
Ripcord applied to all cables with jacket thickness of 60 mils or less
Excellent electrical properties
Abrasion and chemical resistant
Sunlight and weather resistant
Meets cold bend test at -25°C
Meets the crush and impact requirements of Type MC
Construction:
Conductor:
14 AWG thru 750 kcmil bare, annealed copper per ASTM B3
Class B stranding per ASTM B8
Insulation:
Flame retardant Cross-Linked Polyethylene (XLPE)
Color-coded per ICEA Method 4; Individual conductors colored black with conductor number surface printed in contrasting ink
Ground:
Uninaulated bare annealed copper per ASTM B3
Class B stranding per ASTM B8
Jacket:
Flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)
XLPE/PVC Unshielded Low-Voltage Power Cable Options:
Tinned copper conductor
Class C stranding
Insulated ground conductors
Overall shielded multi conductors
Flame Retardant Ethylene Propylene Rubber (EPR) insulation
Low-lead Hypalon Chlorosulfonated Polyethylene (CSPE) / Elastomer blend
ICEA 1000V rated cable
Other constructions available upon request
Approvals:
Industry Approvals
UL 44 Type XHHW-2
UL 1277 Type TC-ER
UL 1581
ICEA S-95-658/NEMA WC70
Flame Tests Approvals
UL 1581 VW-1
UL 1277
IEEE 383
IEEE 1202
CSA FT4
Other Compliances:
Meets EPA 10 CFR, Part 261 for leachable lead content per TCLP method
OSHA acceptable
Product Parameter
AWG Size |
No. of Cond. |
Conductor Stranding |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. (in) |
Ground AWG Size |
Approx LBS/MFT |
14 |
3 |
19/0.0242 |
0.03 |
0.045 |
0.425 |
14 |
116 |
12 |
3 |
19/0.0305 |
0.03 |
0.045 |
0.475 |
12 |
157 |
10 |
3 |
7/0.0385 |
0.03 |
0.06 |
0.515 |
10 |
236 |
8 |
3 |
7/0.0486 |
0.045 |
0.06 |
0.64 |
10 |
314 |
8 |
4 |
7/0.0486 |
0.045 |
0.06 |
0.705 |
10 |
385 |
6 |
3 |
7/0.0612 |
0.045 |
0.06 |
0.72 |
8 |
445 |
6 |
4 |
7/0.0612 |
0.045 |
0.06 |
0.79 |
8 |
558 |
4 |
3 |
7/0.0772 |
0.045 |
0.08 |
0.875 |
8 |
653 |
4 |
4 |
7/0.0772 |
0.045 |
0.08 |
0.95 |
8 |
820 |
2 |
3 |
7/0.0974 |
0.045 |
0.08 |
1 |
6 |
964 |
2 |
4 |
7/0.0974 |
0.045 |
0.08 |
1.095 |
6 |
1214 |
1 |
3 |
19/0.0664 |
0.055 |
0.08 |
1.12 |
6 |
1199 |
1 |
4 |
19/0.0664 |
0.055 |
0.08 |
1.235 |
6 |
1704 |
1/0 |
3 |
19/0.0745 |
0.055 |
0.08 |
1.215 |
6 |
1414 |
1/0 |
4 |
19/0.0745 |
0.055 |
0.08 |
1.34 |
6 |
1825 |
2/0 |
3 |
19/0.0837 |
0.055 |
0.08 |
1.31 |
6 |
1706 |
2/0 |
4 |
19/0.0837 |
0.055 |
0.08 |
1.45 |
6 |
2223 |
3/0 |
3 |
19/0.0940 |
0.055 |
0.08 |
1.42 |
4 |
2437 |
3/0 |
4 |
19/0.0940 |
0.055 |
0.08 |
1.57 |
4 |
3123 |
4/0 |
3 |
19/0.1055 |
0.055 |
0.08 |
1.54 |
4 |
2600 |
4/0 |
4 |
19/0.1055 |
0.055 |
0.11 |
1.765 |
4 |
3444 |
250 |
3 |
37/0.0822 |
0.065 |
0.11 |
1.75 |
4 |
3142 |
250 |
4 |
37/0.0822 |
0.065 |
0.11 |
1.93 |
4 |
4048 |
350 |
3 |
37/0.0973 |
0.065 |
0.11 |
1.97 |
3 |
4230 |
350 |
4 |
37/0.0973 |
0.065 |
0.11 |
2.18 |
3 |
5470 |
500 |
3 |
37/0.1162 |
0.065 |
0.11 |
2.25 |
2 |
5829 |
500 |
4 |
37/0.1162 |
0.065 |
0.11 |
2.45 |
2 |
7579 |
750 |
3 |
61/0.1109 |
0.08 |
0.14 |
2.81 |
1 |
9101 |
750 |
4 |
61/0.1109 |
0.08 |
0.14 |
3.115 |
1 |
11746 |
XLPE/PVC Shielded Low-Voltage Power Cable
Applications:
For use in AC motors controlled by Pulse Width Modulated Inverters, in VFD applications rated up to 2000 Volts. These motor drive systems require cables that are designed to prevent radio frequency interference (RFI) which can lead to malfunction.
In raceways, cable tray or direct burial
In wet or dry locations
Permitted for use in Class I, Div 2 industrial hazardous locations per NEC
Permitted for Exposed Run 'ER' use in accordance with NEC
Features:
Rated at 90°C wet or dry
Dual shield provides maximum shield coverage required for Variable Frequency Drive (VFD) applications
Meets crush and impact requirements to Type MC cable
Excellent electrical properties
Abrasion and chemical resistant
Sunlight and weather resistant
Construction:
Conductor:
14 AWG thru 500 kcmil fully annealed tinned stranded copper
Class B stranding per ASTM B8
Insulation:
Flame retardant Cross-Linked Polyethylene (XLPE) - 90°, VW-1
Color-coded per ICEA Method 4; Individual conductors colored black with conductor number surface printed in contrasting ink
Ground:
3 symmetrically placed annealed tinned copper conductors in direct contact with shield
Class B stranding per ASTM B8
Dual Shield:
Overall tinned copper braided shield in conjunction with an aluminum/polymer tape shield
Jacket:
Flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC) - Black
Approvals:
Industry Approvals
UL 1277 Type TC-ER
UL Type RHH or RHW-2 conductors per UL 44
Flame Tests Approvals
IEEE 383
IEEE 1202
Other Compliances:
Meets EPA 10 CFR, Part 261 for leachable lead content per TCLP method
OSHA acceptable
Product Parameter
AWG Size |
No. of Cond. |
Conductor Stranding |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. (in) |
Ground AWG Size |
Approx LBS/MFT |
14 |
3 |
19/0.0242 |
0.06 |
0.06 |
0.565 |
18 |
190 |
12 |
3 |
19/0.0305 |
0.06 |
0.06 |
0.605 |
16 |
236 |
10 |
3 |
7/0.0385 |
0.06 |
0.06 |
0.665 |
14 |
313 |
8 |
3 |
7/0.0486 |
0.07 |
0.06 |
0.785 |
14 |
420 |
6 |
3 |
7/0.0612 |
0.07 |
0.08 |
0.91 |
12 |
605 |
4 |
3 |
7/0.0772 |
0.07 |
0.08 |
1.01 |
12 |
800 |
2 |
3 |
7/0.0974 |
0.07 |
0.08 |
1.315 |
10 |
1126 |
1/0 |
3 |
19/0.0745 |
0.09 |
0.08 |
1.39 |
10 |
1677 |
2/0 |
3 |
19/0.0837 |
0.09 |
0.08 |
1.49 |
10 |
1979 |
3/0 |
3 |
19/0.0940 |
0.09 |
0.08 |
1.595 |
8 |
2397 |
4/0 |
3 |
19/0.1055 |
0.09 |
0.11 |
1.775 |
8 |
3015 |
250 |
3 |
37/0.0822 |
0.105 |
0.11 |
1.94 |
8 |
3487 |
350 |
3 |
37/0.0973 |
0.105 |
0.11 |
2.16 |
6 |
4661 |
500 |
3 |
37/0.1162 |
0.105 |
0.11 |
2.44 |
6 |
6268 |
XLPE/ARCTIC-FLEX Unshielded Control Cable
Applications:
Industrial lighting, control and signaling circuits
Approved for direct burial, Class I, Div 2 industrial hazardous locations per NEC for UL Type TC cables. In Canada, protection may be required by inspection authority per Canadian electrical code.
Permitted for Exposed Run 'ER' use in accordance with NEC for 3 or more conductors
Approved for cable in tray, industrial hazardous locations, Class I, Zone 2 and Class II, Division 2 per CEC rules 18-156 and 18-252 when used with certified HL glands.
Features:
Rated at 90°C wet or dry
Ripcord applied to all cables with jacket thickness of 60 mils or less
Meets CSA cold impact test at -40°C
Meets ICEA and CSA cold bend test at -65°C
Meets the crush and impact requirements of Type MC
Construction:
Conductor:
14 AWG thru 10 AWG tinned, annealed copper per ASTM B33
Class B stranding per ASTM B8
Insulation:
Flame retardant Cross-Linked Polyethylene (XLPE) Color Coded per CSA Standard C22.2 as follows:
No. of Cond. |
Color Code |
2 |
Black, White |
3 |
Black, Red, Blue |
4 |
Black, Red, Blue, White |
>5 |
All black |
All conductors for all constructions are alpha-numeric printed
Jacket:
Flame retardant and sunlight resistant Arctic-grade Polyvinyl Chloride (PVC)
XLPE/ARCTIC-FLEX Unshielded Control Cable Options:
Bare copper, class C stranding
Uninsulated ground (bonding) conductors
Overall shielded multi conductors
Optional color code as specified per CSA standard C22.2 No. 38 for two to four conductor cable
Non-UL 1000 volt CSA type RW90 XLPE, CSA Type TC
Other constructions available upon request
Approvals:
Industry Approvals:
ICEA S-73-532
ICEA S-95-658/NEMA WC70
UL 44 Type XHHW-2
UL 1277 Type TC-ER for 3 or more conductors
UL 1581
CSA C22.2 No. 38 XLPE RW90
CSA C22.2 No 230 Type TC
Flame Tests Approvals:
UL 1581 VW-1
UL 1277
IEEE 383
IEEE 1202
CSA FT4
Other Compliances:
Meets EPA 10 CFR, Part 261 for leachable lead content per TCLP method
OSHA acceptable
Product Parameter
XLPE/ARCTIC-FLEX Unshielded Low-Voltage Power Cable
Product Parameter
AWG Size |
No. of Cond. |
Conductor Stranding |
Nom. Insul. Thick. (in) |
Jacket Thick |
Nom. O.D. (in) |
Approx LBS/MFT |
14 |
2 |
19/0.0242 |
0.03 |
0.045 |
0.405 |
71 |
14 |
3 |
19/0.0242 |
0.03 |
0.045 |
0.39 |
90 |
14 |
4 |
19/0.0242 |
0.03 |
0.045 |
0.425 |
113 |
14 |
5 |
19/0.0242 |
0.03 |
0.045 |
0.465 |
140 |
14 |
7 |
19/0.0242 |
0.03 |
0.045 |
0.59 |
176 |
14 |
9 |
19/0.0242 |
0.03 |
0.06 |
0.62 |
245 |
14 |
12 |
19/0.0242 |
0.03 |
0.06 |
0.68 |
302 |
14 |
19 |
19/0.0242 |
0.03 |
0.06 |
0.8 |
460 |
14 |
25 |
19/0.0242 |
0.03 |
0.06 |
0.985 |
641 |
14 |
30 |
19/0.0242 |
0.03 |
0.08 |
1.05 |
740 |
14 |
37 |
19/0.0242 |
0.03 |
0.08 |
1.13 |
888 |
12 |
2 |
19/0.0305 |
0.03 |
0.045 |
0.41 |
96 |
12 |
3 |
19/0.0305 |
0.03 |
0.045 |
0.435 |
125 |
12 |
4 |
19/0.0305 |
0.03 |
0.045 |
0.475 |
157 |
12 |
5 |
19/0.0305 |
0.03 |
0.045 |
0.52 |
191 |
12 |
7 |
19/0.0305 |
0.03 |
0.06 |
0.595 |
260 |
12 |
9 |
19/0.0305 |
0.03 |
0.06 |
0.695 |
340 |
12 |
12 |
19/0.0305 |
0.03 |
0.06 |
0.78 |
429 |
12 |
19 |
19/0.0305 |
0.03 |
0.08 |
0.93 |
681 |
12 |
25 |
19/0.0305 |
0.03 |
0.08 |
1.095 |
885 |
12 |
30 |
19/0.0305 |
0.03 |
0.08 |
1.15 |
1005 |
12 |
37 |
19/0.0305 |
0.03 |
0.08 |
1.24 |
1185 |
10 |
2 |
7/0.0385 |
0.03 |
0.045 |
0.455 |
130 |
10 |
3 |
7/0.0385 |
0.03 |
0.045 |
0.485 |
168 |
10 |
4 |
7/0.0385 |
0.03 |
0.06 |
0.515 |
229 |
10 |
5 |
7/0.0385 |
0.03 |
0.06 |
0.615 |
281 |
10 |
7 |
7/0.0385 |
0.03 |
0.06 |
0.67 |
377 |
10 |
9 |
7/0.0385 |
0.03 |
0.06 |
0.785 |
479 |
10 |
12 |
7/0.0385 |
0.03 |
0.08 |
0.895 |
644 |