Type SHD-GC Three-Conductor Portable Power Cable, TPU Sheath 5kV

Applications

These heavy duty cables are designed for heavy mobile equipment such as drag lines, shovels, dredges, drills and for power feeders.

Standards

  • ICEA S-75-381/NEMA WC 58
  • ASTM B 172
  • ASTM B 33
  • CAN/CSA C22.2 No. 96

Construction

  • Conductors: Stranded annealed tinned copper conductor.
  • Insulation:EPR.
  • Insulation Shield:Tinned copper/textile braid.
  • Ground Check Conductor:Tinned copper conductor with a yellow polypropylene insulation.
  • Grounding Conductor:Tinned copper conductor.
  • Sheath: Thermoplastic Polyurethane (TPU) Jacket, black. Other sheath materials can be offered as an option.

Options

Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.

Two-layer jacket with reinforcing fibre between the two layers can be offered as an option.

Mechanical and Thermal Properties

  • Minimum Bending Radius: 6×OD
  • Maximum Operating Temperature: +90℃

Dimensions and Weight

Construction

No. of Strands

Grounding Conductor Size

Ground Check Conductor Size

Nominal Insulation Thickness

Nominal Sheath Thickness

Nominal Sheath Thickness

Nominal Weight

Ampacity

No. of cores×AWG/kcmil

-

AWG/kcmil

AWG/kcmil

inch

mm

inch

mm

inch

mm

lbs/kft

kg/km

A

3×6

133

10

8

0.110

2.8

0.185

4.7

1.56

39.6

1342

1997

93

3×4

259

8

8

0.110

2.8

0.185

4.7

1.68

42.7

1629

2424

122

3×2

259

6

8

0.110

2.8

0.205

5.2

1.87

47.5

2228

3315

159

3×1

259

5

8

0.110

2.8

0.205

5.2

1.95

49.5

2447

3641

184

3×1/0

266

4

8

0.110

2.8

0.220

5.6

2.08

52.8

2760

4106

211

3×2/0

323

3

8

0.110

2.8

0.220

5.6

2.20

55.9

3238

4818

243

3×3/0

418

2

8

0.110

2.8

0.235

6.0

2.36

59.9

3792

5642

279

3×4/0

532

1

8

0.110

2.8

0.235

6.0

2.50

63.5

4548

6767

321

3×250

627

1/0

6

0.120

3.0

0.250

6.4

2.69

68.3

5427

8074

355

3×350

888

2/0

6

0.120

3.0

0.265

6.7

2.95

74.9

7070

10519

435

3×500

1221

4/0

6

0.120

3.0

0.280

7.1

3.31

84.1

9407

13996

536

Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.