Type SHD-GC Three-Conductor Portable Power Cable, TPU Sheath 25kV

Applications

These heavy duty cables are designed for heavy mobile equipment such as drag lines, shovels, dredges, drills and for power feeders.

Standards

  • ICEA S-75-381/NEMA WC 58
  • ASTM B 172
  • ASTM B 33
  • CAN/CSA C22.2 No. 96

Construction

  • Conductors: Stranded annealed tinned copper conductor.
  • Insulation:EPR.
  • Insulation Shield:Tinned copper/textile braid.
  • Ground Check Conductor:Tinned copper conductor with a yellow polypropylene insulation.
  • Grounding Conductor:Tinned copper conductor.
  • Sheath: Thermoplastic Polyurethane (TPU) Jacket, black. Other sheath materials can be offered as an option.

Options

Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.

Two-layer jacket with reinforcing fibre between the two layers can be offered as an option.

Mechanical and Thermal Properties

  • Minimum Bending Radius: 8×OD
  • Maximum Operating Temperature: +90

Dimensions and Weight

Construction

No. of Strands

Grounding Conductor Size

Ground Check Conductor Size

Nominal Insulation Thickness

Nominal Sheath Thickness

Nominal Sheath Thickness

Nominal Weight

Ampacity

No. of cores×AWG/kcmil

-

AWG/kcmil

AWG/kcmil

inch

mm

inch

mm

inch

mm

lbs/kft

kg/km

A

3×1

259

5

8

0.260

6.6

0.265

6.7

2.95

74.9

4410

6561

191

3×1/0

266

4

8

0.260

6.6

0.265

6.7

3.05

77.5

4866

7240

218

3×2/0

323

3

8

0.260

6.6

0.280

7.1

3.20

81.3

5560

8272

249

3×3/0

418

2

8

0.260

6.6

0.280

7.1

3.33

84.6

6192

9213

286

3×4/0

532

1

8

0.260

6.6

0.295

7.5

3.50

88.9

7110

10578

327

Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.