Type SHD-PCG Three-Conductor Portable Power Cable 5kV

Applications

These heavy duty cables are designed for use on longwall shearers, where three shielded power conductors, three unshielded control conductors, and a grounding conductor are required.

Standards

  • ICEA S-75-381/NEMA WC 58
  • ASTM B 172
  • ASTM B 33
  • CAN/CSA-C22.2 No.96

Construction

  • Conductors: Stranded annealed tinned copper conductor.
  • Insulation:EPR.
  • Insulation Shield:Non-conducting Tape + Tinned copper/textile braid.
  • Control Group (3 Conductors):Tinned copper conductor, EPR insulation and thermosetting sheath. Colour of insulation: Black, white and red.
  • Grounding Conductor:Tinned copper conductor, located in the center of the cable.
  • Sheath: Reinforced extra-heavy-duty Chlorinated Polyethylene(CPE), black. Other sheath materials can be offered upon request.

Options

Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.

Two-layer jacket with reinforcing fibre between the two layers can be offered as an option.

Mechanical and Thermal Properties

  • Minimum Bending Radius: 6×OD
  • Maximum Operating Temperature: +90℃

Dimensions and Weight

Construction

No. of Strands

Grounding Conductor Size

Control Conductor Size

Nominal Insulation Thickness

Nominal Sheath Thickness

Nominal Overall Diameter

Nominal Weight

Ampacity

No. of cores×AWG/kcmil

-

AWG/kcmil

AWG/kcmil

inch

mm

inch

mm

inch

mm

lbs/kft

kg/km

A

3×2

259

4

8

0.11

2.8

0.205

5.2

2.03

51.5

2769

4120

159

3×1

259

4

8

0.11

2.8

0.220

5.6

2.12

53.8

2825

4205

184

3×1/0

266

3

8

0.11

2.8

0.220

5.6

2.27

57.7

3571

5313

211

3×2/0

329

2

8

0.11

2.8

0.220

5.6

2.45

62.2

3774

5615

243

3×3/0

418

1

8

0.11

2.8

0.235

6.0

2.58

65.3

4752

7070

279

3×4/0

532

1/0

6

0.11

2.8

0.250

6.4

2.76

69.9

6030

8971

321