Type SHD Three-Conductor Flat Portable Power Cable 2kV

Applications

These flat parallel cables are designed for use on continuous miners requiringgrounding conductors and metallic shieldingover each conductor.

Standards

  • ICEA S-75-381/NEMA WC 58
  • ASTM B 172
  • ASTM B 33

Construction

  • Conductors: Stranded annealed tinned copper conductor.
  • Insulation:EPR.
  • Insulation Shield:Tinned copper/textile braid.
  • Grounding Conductor:Tinned copper conductor with semi-conductive thermoset compound.
  • Sheath: Reinforced extra-heavy-duty Chlorinated Polyethylene(CPE), black. Other sheath materials can be offered as an option.

Options

Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.

Two-layer jacket with reinforcing fibre between the two layers can be offered as an option.

Mechanical and Thermal Properties

  • Minimum Bending Radius: 6×OD
  • Maximum Operating Temperature: +90℃

Dimensions and Weight

Construction

No. of Strands

Grounding Conductor Size

Nominal Insulation Thickness

Nominal Overall Diameter

Height×Width

Nominal Weight

Ampacity

No. of cores×AWG/kcmil

-

AWG/kcmil

inch

mm

inch

mm

lbs/kft

kg/km

A

3×2

259

6

0.07

1.8

0.94×2.45

23.9×62.2

2243

3338

159

3×1

259

5

0.08

2.0

1.04×2.64

26.4×67.1

2540

3780

184

3×1/0

259

4

0.08

2.0

1.08×2.82

27.4×71.6

2915

4338

211

3×2/0

329

3

0.08

2.0

1.18×2.99

30.0×76.0

3346

4980

243

3×3/0

413

2

0.08

2.0

1.25×3.29

31.8×83.6

3890

5789

279

Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.