Home
About Us
Products
Download
Technical Lib
Contact
Enquiry
Sitemap
Links
 

Alarm & Audio & Electronic Cables

Belden Equivalent Cables

Coaxial Cables

Control Cables

Fiber Optic Cables

Flexible Cables

Instrumentation Cables

Lan Cables
Power Cables
Railway Cables

Robotics

Rolling Stock Cables
Rubber & Crane Cables
Security Cables

Telephone Cables

Airport Cables

Bus Cables

Cable Glands

Data Cable

Heat Detection Cables
High Temperature Cables
Highway Cables
Marine, OIL,GAS & Petrochemical Cables
Special Cables
Spiral Cables
Thermocouple Cables
     
  indoor tight buffer fiber optic cable  
Indoor Used Tight Buffered Fiber
Optical Cable
outdoor multi loose tube fiber optic cable
Outdoor Used Multi Loose Tube
Fiber Optical Cable
 
  Power Cables 

Power Cables

BS 6622 Single Core Armoured 11kV XLPE Stranded Aluminium Conductors

Construction

cross-sectional area mmsq

Minimum average thickness of insulation mm

Nominal diameter over insulation
mm

Nominal thickness of PVC bedding
mm

Nominal number and diameter of armoured wires no./mm

Nominal thickness of PVC oversheath
mm

Nominal overall diameter of cable mm

70

3.4

18.8

1.2

42/1.6

1.9

29.7

95

3.4

20.5

1.2

45/1.6

1.9

31.4

120

3.4

22.0

1.2

47/1.6

2.0

33.1

150

3.4

23.3

1.2

40/2.0

2.1

35.4

185

3.4

25.1

1.2

43/2.0

2.1

37.2

240

3.4

27.3

1.2

46/2.0

2.2

39.8

300

3.4

29.6

1.2

49/2.0

2.3

42.3

400

3.4

32.3

1.2

53/2.0

2.4

45.2

500

3.4

35.2

1.3

46/2.5

2.5

49.5

630

3.4

38.6

1.4

50/2.5

2.6

53.3

Installation

cross-sectional area mmsq

Approximate cable weight kg/m

Nominal drum length
m

Minimum bending radius mm

Nominal internal diameter of ducts mm

70

1.1

1000

450

100

95

1.3

1000

500

100

120

1.4

500

500

100

150

1.7

500

550

100

185

1.9

500

600

100

240

2.1

500

600

100

300

2.4

500

650

100

400

2.8

300

700

100

500

3.5

300

750

100

630

4.1

300

800

100

Electrical Performance

cross-sectional area mmsq

Maximum DC resistance of conductor at 20 ℃ uohms/m

Maximum AC resistance of conductor at 90 ℃ uohms/m

Reactance at 50Hz
uohms/m

Impedance at 50Hz uohms/m

Maximum Capacitace PF/m

Maximum charging current at normal voltage and frequency mA/m

70

443

568

130

583

288

0.58

95

320

410

123

428

323

0.65

120

253

325

118

346

353

0.71

150

206

265

117

291

380

0.76

185

164

211

112

240

416

0.83

240

125

161

109

195

460

0.92

300

100

130

105

168

506

1.01

400

77.8

102

101

144

561

1.12

500

60.5

81

99.8

129

619

1.24

630

46.9

64

96.1

116

698

1.37

Ratings

Cross-sectional area mmsq

Current Ratings

Short circuit ratings

Laid direct in ground
Amps

Drawn into ducts
Amps

Laid in air
Amps

One second short circuit rating of conductor
KA

One second short circuit rating of copper per core
KA

70

210

210

240

6.3

Typically

less

then

1kA

95

250

245

295

8.5

120

280

275

335

11.0

150

315

300

380

13.5

185

355

335

435

17.0

240

405

380

510

22.3

300

455

420

580

28.0

400

510

455

670

36.6

500

570

500

770

46.2

630

640

550

880

58.3